Wilmington, Ohio · United States

AZEK: reliable compressed air with lower energy use

A major retrofit replaced unreliable equipment and improved distribution, storage and control. Utility measurements documented the resulting energy savings.

Read the complete original report

Reported project result

1.44MkWh saved per year

01 · Starting point

The operating challenge

The original installation had eleven compressors across three locations, with two permanently out of service. Limited storage and restricted piping contributed to pressure fluctuations and production risk.

02 · Implementation

What changed

Industrial Air Centers installed four 300-hp compressors, including two VSD units, with Airleader management. Piping, air treatment and storage were upgraded; two older machines remained as backup.

03 · Results

The reported numbers

Annualized energy before
7,831,152 kWh
Annualized energy after
6,386,820 kWh
Annual energy savings
1,444,332 kWh
Annual energy cost savings
$90,993 USD
Peak power before → after
914 → 762 kW

The figures cover the complete retrofit measured by the local utility. They are historical results for this installation and cannot be attributed solely to the controller.