Trulite: stabilizing autoclave and plant air

A Canadian glass plant combined additional storage, suitable compressor sizing and central control to reduce idle running and stabilize its two pressure systems.

Read the complete original report

Reported project result

83%less annual electrical energy
Before 100
After 17
Energy index · baseline = 100

01 · Starting point

The operating challenge

The autoclave and plant operated at different pressures. Insufficient storage caused pressure dips; oversized variable-speed equipment and extended unloaded running increased energy use.

02 · Implementation

What changed

Measured demand and simulation informed the new combination. The project enlarged storage, adapted the compressors and introduced coordinated control and online monitoring.

03 · Results

The reported numbers

Reported annual energy before
2,824,522 kWh
Reported annual energy after
481,122 kWh
Reported annual energy reduction
2,343,400 kWh · 83%
Historical Canadian utility incentive
CAD 147,428

Canadian project, not a US incentive example. Amounts retain their original Canadian currency. The result covers the entire retrofit and cannot be attributed solely to the controller. The source does not establish a current tariff or a generally available rebate.